General Data / Specications
Model Name LMCN077HV LCN097HV4 LCN127HV4 LMCN185HV
Grille (Sold Separately)
PT-QCHW0 /
PT-UQC
PT-QCHW0 /
PT-UQC
PT-QCHW0 /
PT-UQC
PT-QCHW0 /
PT-UQC
Nominal Cooling Capacity (Btu/h)
1
7,000 9,000 12,000 18,000
Nominal Heating Capacity (Btu/h)
1
8,100 10,400 13,800 20,800
Operating Range
Cooling (°F WB)
57-77
Heating (°F DB)
59-81
Fan
Type
Turbo
Motor Output (W) x Qty.
43 x 1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate CFM (H/M/L)
265 / 212 / 177 300 / 265 / 230 335 / 283 / 247 459 / 424 / 388
Unit Data
Refrigerant Type
2
R410A
Refrigerant Control
EEV
Power Supply V, Ø, Hz
3
208-230, 1, 60
Rated Amps (A)
0.25
Sound Pressure Level ±3 dB(A) (H/M/L)
4
31 / 27 / 24 36 / 33 / 30 38 / 35 / 32 38 / 37 / 34
Body Dimensions (W x H x D, in.)
22-7/16 x 8-7/16 x 22-7/16 22-7/16 x 10-3/32 x 22-7/16
Grille (Sold separately) Dimensions (WxHxD, in.)
27-9/16 x 7/8 x 27-9/16
Body Net Weight (lbs.)
31 34
Grille (Sold separately) Net Weight (lbs.)
7
Body Shipping Weight (lbs.)
34 37 42
Grille (Sold separately) Shipping Weight (lbs.)
11 9 9 11
Power Wiring / Communications Cable (No. x AWG)
5
4 x 18
Heat Exchanger (Row x Column x Fin / inch) x Number
(2 x 8 x 18) x 1 (2 x 10 x 18) x 1
Piping
Liquid (in.)
1/4
Vapor (in.)
3/8 1/2
Drain O.D. / I.D. (in.)
1-1/4, 1
1
Nominal capacity is rated 0 ft. above sea level with a 0 ft. level difference between outdoor and indoor
units. All capacities are net with a combination ratio between 95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
This unit comes with a dry helium charge.
3
Acceptable operating voltage: 187V-253V.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
same in both cooling and heating mode. These values can increase due to ambient conditions during
operation.
5
All power wiring / communications cable to the IDUs be minimum 18 AWG, 4-conductor, stranded,
shielded or unshielded (if shielded, must be grounded to chassis at ODU only) and must comply with
applicable local and national codes.
Table 65:Multi F Four-Way Ceiling-Cassette Indoor Unit General Data.
FOUR-WAY CEILING-CASSETTE INDOOR UNITS
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
114 | CEILING-CASSETTE
Multi F and Multi F MAX Indoor Unit Engineering Manual
MULTI
F
MAX
MULTI
F
Vue de la page 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 203 204

Commentaires sur ces manuels

Pas de commentaire