Multi F and Multi F MAX Indoor Unit Engineering Manual
MULTI
F
MAX
MULTI
F
Acoustic Data
STANDARD WALL-MOUNTED INDOOR UNITS
Measurement taken 2.6′ below the bottom of the unit and at a
distance of 3.3′ from face of unit.
Measurements taken with no attenuation and units operating at full
load normal operating condition.
Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
Sound power levels are measured in dB(A)±1.
Tested in anechoic chamber per ISO Standard 3745.
Model No.
Sound Pressure Levels (dB[A]) (Cooling and Heating)
High Fan Speed
Medium Fan
Speed
Low Fan Speed
LMN079HVT 35 31 26
LSN090HSV5 36 32 27
LSN120HSV5 38 34 29
LMN159HVT 42 38 32
LSN180HSV5 44 38 34
LMN249HVT 46 41 36
Figure 63: Sound Pressure Level Measurement Location.
Table 27: Sound Pressure Levels (dB[A]).
2.6 ft.
3.3 ft.
Microphone
Figure 64:LMN079HVT, LSN090HSV5, and LSN120HSV5 Sound Pressure Level Diagrams.
LMN079HVT
LSN090HSV5
LSN120HSV5