INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national
wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading
it thoroughly.your set and retain it for future reference.
P/NO : MFL68460401
http://www.lghvac.com
www.lg.com
ENGLISH
FRANÇAIS
ESPAÑOL
Vue de la page 0
1 2 3 4 5 6 ... 94 95

Résumé du contenu

Page 1 - AIR CONDITIONER

INSTALLATION MANUALAIR CONDITIONER • Please read this installation manual completely before installing the product.• Installation work must be perform

Page 2 - TIPS FOR SAVING ENERGY

10OUTDOOR UNITS INFORMATIONENGLISHChassisUX2+UX3 UX3+UX3HP22 24Ton18 20Model NameCombination UnitARUN216BTE4 ARUN240BTE4Independent UnitARUN144BTE4 AR

Page 3 - IMPORTANT SAFETY INSTRUCTIONS

OUTDOOR UNITS INFORMATION11ENGLISHChassisUX2+UX3+UX3 UX3+UX3+UX3HP32 34Ton26 28Model NameCombination UnitARUN312BTE4 ARUN336BTE4Independent UnitARUN14

Page 4 - Operation

12OUTDOOR UNITS INFORMATIONENGLISHChassisUX3+UX3+UX3 UX3+UX3+UX3HP40 42Ton34 36Model NameCombination UnitARUN408BTE4 ARUN432BTE4Independent UnitARUN12

Page 5 - Installation

OUTDOOR UNITS INFORMATION13ENGLISHModel Name : ARUN***DTE4Power Supply Outdoor Unit (3Ø, 460V, 60Hz)ChassisUX3 UX3HP12 14Ton10 12Model NameCombination

Page 6

14OUTDOOR UNITS INFORMATIONENGLISHChassisUX2+UX3 UX3+UX3HP22 24Ton18 20Model NameCombination UnitARUN216DTE4 ARUN240DTE4Independent UnitARUN144DTE4 AR

Page 7 - TABLE OF CONTENTS

OUTDOOR UNITS INFORMATION15ENGLISHChassisUX2+UX3+UX3 UX3+UX3+UX3HP32 34Ton26 28Model NameCombination UnitARUN312DTE4 ARUN336DTE4Independent UnitARUN14

Page 8 - INSTALLATION PROCESS

16OUTDOOR UNITS INFORMATIONENGLISHChassisUX3+UX3+UX3 UX3+UX3+UX3HP40 42Ton34 36Model NameCombination UnitARUN408DTE4 ARUN432DTE4Independent UnitARUN12

Page 9 - OUTDOOR UNITS INFORMATION

ENVIRONMENT-FRIENDLY ALTERNATIVE REFRIGERANT R410A17ENGLISHCAUTION• The wall thickness of the piping should comply with the relevant local and nationa

Page 10

18SELECT THE BEST LOCATIONENGLISHSelect space for installing outdoor unit, which will meet the following conditions:• No direct thermal radiation from

Page 11

INSTALLATION SPACE19ENGLISHIndividual InstallationDuring the installation of the unit, consider service, inlet, and outlet and acquire the minimumspac

Page 12

• Do not cool excessively indoors. This may be harmful for your health and may consume moreelectricity.• Block sunlight with blinds or curtains whil

Page 13 - Model Name : ARUN***DTE4

20INSTALLATION SPACEENGLISHSeasonal wind and cautions in winter• Sufficient measures are required in a snow area or severe cold area in winter so that

Page 14

LIFTING METHOD21ENGLISHCAUTIONBe very careful while carrying the product.• Do not have only one person carry product if it is more than 20 kg(44lbs).•

Page 15

22INSTALLATIONENGLISHThe location of the Anchor bolts• Install at places where it can endure the weight and vibration/noise of the outdoor unit.• The

Page 16

INSTALLATION23ENGLISHFoundation for Installation• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquakeor g

Page 17 - ALTERNATIVE REFRIGERANT R410A

24INSTALLATIONENGLISHMain cause of gas leakage is defect in flaring work. Carry out correct flaring work in the followingprocedure.Cut the pipes and t

Page 18 - SELECT THE BEST LOCATION

INSTALLATION25ENGLISHFlare shape and flare nut tightening torqueOpening shutoff valvePrecautions when connecting pipes- See the following table for fla

Page 19 - INSTALLATION SPACE

26INSTALLATIONENGLISH1Use the heat insulation material for the refrigerant piping which has an excellentheat-resistance (over 248°F).2Precautions in h

Page 20

INSTALLATION27ENGLISHPlumbing materials and storage methodsPipe must be able to obtain the specified thickness and should be used with low impurities.

Page 21 - Forklift Carrying Hole

28INSTALLATIONENGLISHNitrogen substitution methodWelding, as when heating without nitrogen substitution a large amount of the oxide film isformed on

Page 22 - INSTALLATION

REFRIGERANT PIPING INSTALLATION29ENGLISHPrecautions on Pipe connection / Valve operationPipe connection is done by connecting from the end of the pipe

Page 23 - Foundation for Installation

3IMPORTANT SAFETY INSTRUCTIONSENGLISHIMPORTANT SAFETY INSTRUCTIONSREAD ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.Always comply with the following pr

Page 24 - Preparation of Piping

30PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISH- Pipe connections can be done on the front side or on the side according to the installation

Page 25 - Opening shutoff valve

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT31ENGLISHRemove leakage prevention cap• Remove the leakage prevention cap attached to the outdoor unit

Page 26 - Closing shutoff valve

32PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISHMethod of drawing out pipes on the bottom side- Drawing out common pipe through side panelLiq

Page 27 - Moisture

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT33ENGLISHY branch method1 Outdoor UnitsExample : 5 Indoor Units connectedⒶ : Outdoor UnitⒷ : 1st branc

Page 28 - Nitrogen substitution method

34PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISH3 Outdoor UnitsExample : 5 Indoor Units connectedⒶ : Outdoor UnitⒷ : 1st branch (Y branch) Ⓒ

Page 29 - Charging Port

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT35ENGLISHRefrigerant pipe diameter from branch to branch (B,C,D)• * : Assume equivalent piping length

Page 30 - OUTDOOR UNIT

36PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISHRefrigerant pipe diameter from outdoor unit to first branch. (A)Upward Out-door unittotal cap

Page 31

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT37ENGLISH3 Outdoor UnitsExample : 6 Indoor Units connectedⒶ : Outdoor UnitⒷ : Header branchⒸ : Indoor

Page 32 - Liquid pipe Gas pipe

38PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISH• * : Assume equivalent piping length of Y branch to be 0.5m(1.64ft), that of header to be1m(

Page 33 - Refrigerant piping system

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT39ENGLISH3 Outdoor UnitsExample : 5 Indoor Units connectedⒶ : Outdoor UnitⒷ : 1st branch(Y branch)Ⓒ :

Page 34

• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compressair or Oxygen and do not use Flammable gases. Otherwis

Page 35

40PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISH• * : Assume equivalent piping length of Y branch to be 0.5m(1.64ft), that of header to be1

Page 36 - Header Method

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT41ENGLISHOutdoor unit ConnectionIndoor Unit ConnectionIndoor Unit connecting pipe from branch (a,b,c,d

Page 37 - Master ≥ Slave1 ≥ Slave2

42PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISHPipe Connection Method/Precautions for Series connections between Outdoor units- Separate Y b

Page 38

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT43ENGLISH- The pipes between the outdoor units must maintain horizontal levelness or give an inclinati

Page 39

44PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISH- When connecting the pipes between the outdoor units, the accumulation of oil in the slave o

Page 40

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT45ENGLISHThe amount of RefrigerantThe calculation of the additional charge should take into account th

Page 41 - Indoor Unit Connection

46PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISHWARNING• Regulation for refrigerant leakage: the amount of refrigerant leakage should satisf

Page 42

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT47ENGLISH- Ensure that the branch pipes are attached vertically.HeaderSlaveMasterSlaveMasterSlaveMaste

Page 43

48PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISHY branchHeaderA B FacingupwardsFacingdownwardsWithin 3˚ Within 3˚Viewed from point Ain direct

Page 44

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT49ENGLISH• When the number of indoor units to be connected to the branch pipes is less than the number

Page 45 - The amount of Refrigerant

IMPORTANT SAFETY INSTRUCTIONS5ENGLISHCAUTIONInstallation• Always check for gas (refrigerant) leakage after installation or repair of product.- Low ref

Page 46 - Refrigerant charging

50PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISHY branch pipeModels Gas pipe Liquid pipeARBLN01621I.D19.05(3/4)O.D15.88(5/8)I.D12.7(1/2)I.D15

Page 47 - Distribution Method

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT51ENGLISHHeaderModels Gas pipe Liquid pipe4 branchARBL054ID12.7(1/2)ID15.88(5/8)360(14-5/32)120(4-23/3

Page 48 - Branch pipe Fitting

52PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISHLeak testLeak test should be made by pressurizing nitrogen gas to 3.8 MPa(551.1psi). If the p

Page 49 - Insulator for cap pipe

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT53ENGLISHVacuumVacuum drying should be made from the service port provided on the outdoor unit’s servi

Page 50 - Y branch pipe

54PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITENGLISHThis function is used for creating vacuum in the system after compressor replacement, ODUpart

Page 51

PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT55ENGLISHBe sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe se

Page 52 - Leak Test and Vacuum drying

56ELECTRICAL WIRINGENGLISHCaution- Follow ordinance of your governmental organization for technical standard related to electricalequipment, wiring re

Page 53 - Gas side

ELECTRICAL WIRING57ENGLISH2-Core Shield Cable Multi-Core CableMaster Slave1 Slave2RemotecontrollerRemotecontrollerIndoorUnitIndoorUnitRemotecontroller

Page 54 - Vacuum Mode

58ELECTRICAL WIRINGENGLISHControl box and connecting position of wiring- Remove all of the screws at front panel and remove the panel by pulling it fo

Page 55 - (3.28ft)

ELECTRICAL WIRING59ENGLISHCommunication and Power CablesCommunication cable- Types : shielding cable- Cross section : 1.0~1.5mm2(1.55x10-3~2.32x10-3in

Page 56 - ELECTRICAL WIRING

6IMPORTANT SAFETY INSTRUCTIONSENGLISH• Safely dispose of the packing materials.- Packing materials, such as nails and other metal or wooden parts, may

Page 57 - Power cable

60ELECTRICAL WIRINGENGLISHWiring of main power supply and equipment capacity- Use a separate power supply for the Outdoor Unit and Indoor Unit.- Bear

Page 58 - Front Panel

ELECTRICAL WIRING61ENGLISHField Wiring(3Ø, 208/230V)60HzExample Connection of Communication Cable• 1 Outdoor Unit - 3Ø, 208/230VL N Communication Line

Page 59

62ELECTRICAL WIRINGENGLISHNOTE!- Field Wiring diagram is to be used as a guidelineonly. Wiring should comply with applica-ble local and national codes

Page 60

ELECTRICAL WIRING63ENGLISHNOTE!- Field Wiring diagram is to be used as a guidelineonly. Wiring should comply with applica-ble local and national codes

Page 61 - Field Wiring(3Ø, 208/230V)

64ELECTRICAL WIRINGENGLISHWARNING• Indoor Unit ground Lines are required for preventing electrical shock accident during cur-rent leakage, Communicati

Page 62 - 34 34 34

ELECTRICAL WIRING65ENGLISHNOTE!- Field Wiring diagram is to be used as a guidelineonly. Wiring should comply with applica-ble local and national codes

Page 63 - (Main Switch)

66ELECTRICAL WIRINGENGLISHWARNING• Indoor Unit ground Lines are required for preventing electrical shock accident during cur-rent leakage, Communicati

Page 64 - Outdoor unit

ELECTRICAL WIRING67ENGLISHField Wiring(3Ø, 460V)60HzExample Connection of Communication Cable• 1 Outdoor Unit - 3Ø, 460VL N Communication Line (2 Wire

Page 65

68ELECTRICAL WIRINGENGLISHNOTE!- Field Wiring diagram is to be used as a guideline only. Wiring should comply with applica-ble local and national code

Page 66

ELECTRICAL WIRING69ENGLISHNOTE!- Field Wiring diagram is to be used as a guideline only. Wiring should comply with applica-ble local and national code

Page 67 - Field Wiring(3Ø, 460V)

72 TIPS FOR SAVINGENERGY3 IMPORTANT SAFETYINSTRUCTIONS8 INSTALLATIONPROCESS9 OUTDOOR UNITSINFORMATION17 ALTERNATIVE REFRIG-ERANT R410A18 SELECT THE BE

Page 68 - Outdoor Unit

70ELECTRICAL WIRINGENGLISHWARNING• Indoor Unit ground Lines are required for preventing electrical shock accident during cur-rent leakage, Communicati

Page 69

ELECTRICAL WIRING71ENGLISHNOTE!- Field Wiring diagram is to be used as a guideline only. Wiring should comply with applica-ble local and national code

Page 70

72ELECTRICAL WIRINGENGLISHWARNING• Indoor Unit ground Lines are required for preventing electrical shock accident during cur-rent leakage, Communicati

Page 71

ELECTRICAL WIRING73ENGLISH• Example Connection of Transmission Cable[BUS type]- Connection of transmission cable must beinstalled like below figure be

Page 72

74ELECTRICAL WIRINGENGLISHCAUTIONIt should be wiring power cables or communication cables to avoid interference with the oil levelsensor. Otherwise, T

Page 73

ELECTRICAL WIRING75ENGLISHCAUTIONIt should be wiring power cables or communication cables to avoid interference with the oil levelsensor. Otherwise, T

Page 74

76ELECTRICAL WIRINGENGLISHChecking the setting of outdoor unitsChecking according to dip switch setting - You can check the setting values of the Mast

Page 75

ELECTRICAL WIRING77ENGLISHAutomatic AddressingThe address of indoor units would be set by Automatic Addressing- Wait for 3 minutes after supplying pow

Page 76

78ELECTRICAL WIRINGENGLISHThe Procedure of Automatic Addressing• Automatic addressing setting endNumbers of indoor unit connection set whose addressin

Page 77 - Automatic Addressing

ELECTRICAL WIRING79ENGLISHMODE FUNCTION OPTION VALUE ACTIONremarkscon-tentDisplay1contentDisplay2content Display3con-tentDisplay4implement Display5In-

Page 78

8INSTALLATION PROCESSENGLISHThe foundation must be level evenOutdoor unit foundation workAvoid short circuits and ensure sufficient space is allowed fo

Page 79

80ELECTRICAL WIRINGENGLISHGroup Number settingGroup Number setting for Indoor Units- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is O

Page 80 - B(D) A(C) BA

TEST RUN81ENGLISHCool & Heat selectormode setting methodMaster unit PCB DIP switch on : No.5Select the mode using ‘▶’, ‘◀’ Button :“Func” Push the

Page 81 - TEST RUN

82TEST RUNENGLISHStatic pressure compensation modeThis function secures the air flow rate of ODU, in case static pressure has been applied like usingd

Page 82

TEST RUN83ENGLISHNight Low Noise FunctionIn cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise ofODU at night wh

Page 83 - Night Low Noise Function

84TEST RUNENGLISHOverall defrost modemode setting methodMaster unit PCB DIP switch on : No.5Select the mode using ‘▶’, ‘◀’ Button :“Func” Push the ‘●’

Page 84 - Overall defrost mode

TEST RUN85ENGLISHSetting the ODU addressmode setting methodMaster unit PCB DIP switch on : No.5Select the mode using ‘▶’, ‘◀’ Button :“Func” Push the

Page 85 - Setting the ODU address

86TEST RUNENGLISHSnow removal & rapid defrostmode setting methodMaster unit PCB DIP switch on : No.5Select the mode using ‘▶’, ‘◀’ Button :“Func”

Page 86

TEST RUN87ENGLISHTarget pressure adjustingmode setting methodMaster unit PCB DIP switch on : No.5Select the mode using ‘▶’, ‘◀’ Button :“Func” Push th

Page 87 - Target pressure adjusting

88TEST RUNENGLISHSelf-Diagnosis FunctionError Indicator- This function indicates types of failure in self-diagnosis and occurrence of failure for air

Page 88 - Error No. of Unit

TEST RUN89ENGLISHDisplay Title Cause of ErrorOutdoor unit related error3 4 *High Pressure of Master Outdoor Unit High Pressure of Master Outdoor Unit3

Page 89

OUTDOOR UNITS INFORMATION9ENGLISHCAUTIONNotes : * We can guarantee the operation only within 130% Combination.If you want to connect more than 130% co

Page 90

90TEST RUNENGLISHDisplay Title Cause of ErrorOutdoor unit related error1 0 4*Communication Error BetweenMaster Outdoor Unit and OtherOutdoor UnitFaili

Page 91 - CAUTION FOR REFRIGERANT LEAK

CAUTION FOR REFRIGERANT LEAK91ENGLISHChecking procedure of limiting concentrationCheck limiting concentration along following steps and take appropria

Page 92 - Smallest

92CAUTION FOR REFRIGERANT LEAKENGLISH- With partition and without opening which serve as passage of air to adjoining roomCalculate refrigerant concent

Page 93 - Windbreak

INSTALLATION GUIDE AT THE SEASIDE93ENGLISHSelecting the location(Outdoor Unit)If the outdoor unit is to be installed close tothe seaside, direct expos

Page 94

94ENGLISH

Page 95

US1. Please call the installing contractor of your product, as warranty service will be provided by them.2. If you have service issues that have not b