24
ENGLISH
(Table 2) Refrigerant pipe diameter from outdoor unit to first branch. (A)
ODU
capacity
(hp)
Pipe diameter when pipe
length is < 90m (295ft)
(Standard)
Pipe diameter when pipe
length is 90m (295ft)
Pipe diameter when height differ-
ential (ODU÷IDU) is > 50m (164ft)
Liquid Pipe
mm (inch)
Gas Pipe
mm (inch)
Liquid Pipe
mm (inch)
Gas Pipe
mm (inch)
Liquid Pipe
mm (inch)
Gas Pipe
mm (inch)
8
Ø9.52 (3/8) Ø19.05 (3/4) Ø12.7 (1/2) Ø22.2 (7/8) Ø12.7 (1/2) Not increased
10
Ø9.52 (3/8) Ø22.2 (7/8) Ø12.7 (1/2) Ø28.58 (1-1/8) Ø12.7 (1/2) Not increased
12~16
Ø12.7 (1/2) Ø28.58 (1-1/8) Ø15.88 (5/8) Ø34.9 (1-3/8) Ø15.88 (5/8) Not increased
18~22
Ø15.88 (5/8) Ø28.58 (1-1/8) Ø19.05 (3/4) Ø34.9 (1-3/8) Ø19.05 (3/4) Not increased
24
Ø15.88 (5/8) Ø34.9 (1-3/8) Ø19.05 (3/4) Ø41.3 (1-5/8) Ø19.05 (3/4) Not increased
26~34
Ø19.05 (3/4) Ø34.9 (1-3/8) Ø22.2 (7/8) Ø41.3 (1-5/8) Ø22.2 (7/8) Not increased
36~60
Ø19.05 (3/4) Ø41.3 (1-5/8) Ø22.2 (7/8) Ø44.5 (1-3/4) Ø22.2 (7/8) Not increased
62~64
Ø22.2 (7/8) Ø44.5 (1-3/4) Ø25.4 (1) Ø53.98 (2-1/8) Ø25.4 (1) Not increased
66~96
Ø22.2 (7/8) Ø53.98 (2-1/8) Ø25.4 (1) Ø53.98 (2-1/8) Ø25.4 (1) Not increased
Outdoor unit Connection
WARNING
• In case of pipe diameter B connected after first branch is bigger
than the main pipe diameter A, B should be of the same size
with A.
Ex) In case indoor unit combination ratio 120% is connected to
70kW outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(1-3/8))(Low
pressure gas pipe), Ø15.88(5/8)(liquid pipe), Ø28.58(1-
1/8)(High Pressure liquid pipe)
2) Pipe diameter B after first branch according to 120% in-
door unit combination(84kW) : Ø34.9(1-3/8)(Low pressure
gas pipe), Ø19.05(3/4)(liquid pipe), Ø28.58(1-1/8)(High
Pressure liquid pipe)
Therefore, pipe diameter B connected after first branch
would be Ø34.9(1-3/8)(Low pressure gas pipe),
Ø15.88(5/8)(liquid pipe), Ø28.58(1-1/8)(High Pressure liq-
uid pipe) which is same with main pipe diameter.
[Example]
Do not choose the main pipe diameter by downward indoor unit
total capacity but its outdoor unit model name.
Do not let the connection pipe from branch to branch exceed the
main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 22 HP (61.5 kW)
outdoor unit to 120% of its system capacity (73.8 kW) and
branching 7k (2.1kW) indoor unit at the 1st branch
Main pipe diameter(22 HP outdoor unit): Ø28.58(1-1/8)(Low pres-
sure gas pipe), Ø15.88(5/8)(Liquid pipe), Ø22.2(7/8)(High pressure
gas pipe)
Pipe diameter between 1st and 2nd branch (71.7kW indoor units):
Ø34.9(1-3/8)(Gas pipe) Ø19.05(3/4)(Liquid pipe) in conformity with
Downward indoor units.
Since the main pipe diameter of 22HP outdoor unit is Ø28.58(1-
1/8)(Low pressure gas pipe), Ø15.88(5/8)(Liquid pipe), Ø22.2(7/8)
(High pressure gas pipe) is used as the main pipe and the connec-
tion pipe between 1st and 2nd branch.
!
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe [mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
< 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
< 28.0(95,900) Ø9.52(3/8) Ø22.2(7/8)
(Table 3) Refrigerant pipe diameter from first branch to last branch (B,C,D)
Downward indoor unit
total capacity [kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0 (54,600) Ø9.52(3/8) Ø15.88(5/8)
22.4 (76,400)
Ø9.52(3/8) Ø19.05(3/4)
< 33.6 (114,700) Ø9.52(3/8) Ø22.2(7/8)
< 50.4 (172,000) Ø12.7(1/2) Ø28.58(1-1/8)
< 67.2 (229,400) Ø15.88(5/8) Ø28.58(1-1/8)
< 72.8(248,500) Ø15.88(5/8) Ø34.9(1-3/8)
< 100.8(344,000) Ø19.05(3/4) Ø34.9(1-3/8)
< 173.6(592,500) Ø19.05(3/4) Ø41.3(1-5/8)
< 184.8(630,700) Ø22.2(7/8) Ø44.5(1-3/4)
224.0(764,400)
Ø22.2(7/8) Ø53.98(2-1/8)
(Table 4) Conditional Application
WARNING
• In case of pipe diameter B connected after first branch is bigger
than the main pipe diameter A, B should be of the same size
with A.
Ex) In case indoor unit combination ratio 120% is connected to
24HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(1-3/8)(Gas pipe),
Ø15.88(5/8)(liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor
unit combination(80.6kW) : Ø34.9(1-3/8)(gas pipe),
Ø19.05(3/4)(liquid pipe)
Therefore, pipe diameter B connected after first branch
would be Ø34.9(1-3/8)(gas pipe) / Ø15.88(5/8)(liquid pipe)
which is same with main pipe diameter.
!
Condition Example
1
Diameter of pipes be-
tween first branch and the
last branch should be in-
creased by one step, ex-
cept pipe diameter B,C,D
is same as Diameter A
40 m [131 ft] <
B+C+D+e
90 m [295 ft]
B, C, D
Change a diameter
2
While calculating whole re-
frigerant pipe length, pipe
B,C,D length should be cal-
culated twice.
A+Bx2+Cx2+Dx2
+a+b+c+d+e
1 000 m [3 281 ft]
3
Length of pipe from each
indoor unit to the closest
branch
a,b,c,d,e
40 m
[131 ft]
4
Length of pipe from out-
door unit to the farthest
indoor unit 5
(A+B+C+D+e)] - [Length
of pipe outdoor unit to the
closest indoor unit 1
(A+a)]
40 m [131 ft]
(A+B+C+D+e)-
(A+a) 40 m
[131 ft]
• To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
Ø6.35(1/4) Ø9.52(3/8), Ø9.52(3/8)
Ø12.7(1/2), Ø12.7(1/2) Ø15.88(5/8),
Ø15.88(5/8) Ø19.05(3/4), Ø19.05(3/4)
Ø22.2(7/8), Ø22.2(7/8) Ø25.4(1),
Ø25.4(1) Ø28.58(1-1/8), Ø28.58(1-1/8)
Ø31.8(1-1/4), Ø31.8(1-1/4) Ø34.9(1-3/8),
Ø34.9(1-3/8) Ø38.1(1-1/2)
l
h 40 m [131 ft]
H 110 m [361 ft]
L
Indoor
Unit
1,MFL67221433,영어 2017. 7. 5. 오전 10:31 페이지 24