ENGLISH
S/W No. Setup
No.1 Manual addressing of valve #1
No.2 Manual addressing of valve #2
No.3 Manual addressing of valve #3
No.4 Manual addressing of valve #4
SW03M
Increase in the digit of 10 of valve ad-
dress
SW04M Increase in the last digit of valve address
SW05M Manual addressing of zoning indoor units
SW01M
SW03M
SW04M
SW05M
Dip switch
7 segment
SW01C
(Automatic Addressing Setting)
The Procedure of Automatic Addressing
• Automatic addressing process end Numbers of indoor
unit connected are indicated for 30seconds on
7-segment LED after completing process
Indoor address number is displayed on wired remote controller or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote controller
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
and Automatic addressing is completed normally.
Automatic Addressing process start
Waiting 3 minutes
Power On
Press RED Button for 5 s
(SW01C)
7-segment LED = 88
Don’t press RED Button
(SW01C)
Waiting about 2~7 minutes
7-segment LED
OK
YES
NO Check the connections
of communication cable
= 88
CAUTION
• In replacement of the indoor unit PCB, always perform Automatic
addressing setting again (At that time, please check about using In-
dependent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error
occur.
• Automatic Addressing has to be performed after more than 3 min-
utes to improve indoor unit communition when initial power is sup-
plied.
• Please be sure that all the dip switch (1~7) of master outdoor unit is
OFF before Automatic Addressing setting
!
Automatic Addressing
The address of indoor units would be set by Automatic
Addressing
- Wait for 3 minutes after supplying power.
(Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A “88” is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on
numbers of connected indoor units
-
Numbers of connected indoor units whose addressing is completed are
indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated
on the wired remote control display window. (CH01, CH02,
CH03, ……, CH06 : Indicated as numbers of connected indoor units)